Section 6: Reinforcing Steel
Anchor: #i1019916Table of Standard Reinforcing Steel Bars
On quantity tables, show the length to the nearest inch and the weight to the nearest pound.
|
English Designations |
Nom Bar Dia (Inches) |
Weight (Lbs per LF) |
Area (Sq Inches) |
|
|---|---|---|---|---|
|
#3 |
0.375 |
3/8 |
0.376 |
0.110 |
|
#4 |
0.500 |
1/2 |
0.668 |
0.196 |
|
#5 |
0.625 |
5/8 |
1.043 |
0.307 |
|
#6 |
0.750 |
3/4 |
1.502 |
0.442 |
|
#7 |
0.875 |
7/8 |
2.044 |
0.601 |
|
#8 |
1.000 |
1 |
2.670 |
0.785 |
|
#9 |
1.128 |
1 1/8 |
3.400 |
1.000 |
|
#10 |
1.270 |
1 1/4 |
4.303 |
1.266 |
|
#11 |
1.410 |
1 3/8 |
5.313 |
1.563 |
|
#14 |
1.693 |
1 3/4 |
7.650 |
2.250 |
|
#18 |
2.257 |
2 1/4 |
13.600 |
4.000 |
|
1 1/4" Dia Smooth |
1.250 |
1 1/4 |
4.172 |
1.227 |
Anchor: #i1019925
Bar Labels
For bar labels, use upper case letters according to the designations listed in Table 1-8 where possible. Letters not designated may be used as necessary.
Lowercase prefix letters may be used to identify bars in sub-components such as wings. Examples are wH, wV, wU, and wS or wP bars in wingwalls. Prefix letters should be used only where there is a definite improvement in clarity from flagging the steel in sub-components separately from other reinforcing steel.
See individual chapters for detail examples of the normal bar designations.
|
Label |
Description |
|---|---|
|
A |
Main bars top and bottom or Main bars top |
|
B |
Main bars bottom (Slabs on stringers or caps) |
|
C |
|
|
D |
Distribution bars or dowels |
|
E |
Cap pedestal bars |
|
F |
Footings |
|
G |
|
|
H |
Horizontal bars |
|
I |
(do not use) |
|
J |
Shape |
|
K |
|
|
L |
Shape |
|
M |
|
|
N |
|
|
O |
(do not use) |
|
P |
|
|
Q |
(not preferred) |
|
R |
|
|
S |
Stirrups |
|
T |
Temperature steel |
|
U |
Shape |
|
V |
Vertical bars |
|
W |
|
|
X |
Slab dowels |
|
Y |
|
|
Z |
Spiral bars |
Anchor: #i1019944
English Development Length and Splices
Class B splice – 50 percent or less of the bars spliced at one location* (except conventional slab reinforcing) * Epoxy coated splice lengths by designing engineer (round up to even inch)
|
Size |
A Ld |
B 1.3 Ld |
C 1.3 (1.4) Ld |
D 1.3 (1.4) 0.8 Ld |
E 1.3 (0.8) Ld |
|---|---|---|---|---|---|
|
Grade 40 fy=40,000 psi f 'c=3,600 psi (Class C Concrete) |
|||||
|
#3 |
(6.00") 1' – 0" |
1' – 0" |
1' – 0" |
1' – 0" |
1' – 0" |
|
#4 |
(8.00") 1' – 0" |
1' – 0" |
1' – 3" |
1' – 0" |
1' – 0" |
|
#5 |
(10.00") 1' – 0" |
1' – 1" |
1' – 7" |
1' – 3" |
1' – 0" |
|
#6 |
(12.00") 1' – 0" |
1' – 4" |
1' – 10" |
1' – 6" |
1' – 1" |
|
#7 |
(16.03") 1' – 5" |
1' – 9" |
2' – 6" |
2' – 0" |
1' – 5" |
|
#8 |
(20.93") 1' – 9" |
2' – 4" |
3' – 3" |
2' – 7" |
1' – 10" |
|
#9 |
(26.67") 2' – 3" |
2' –11" |
4' – 1" |
3' – 3" |
2' – 4" |
|
#10 |
(33.76") 2' – 10" |
3' – 8" |
5' – 2" |
4' – 2" |
3' – 0" |
|
#11 |
(41.68") 3' – 6" |
4' – 7" |
6' – 4" |
5' – 1" |
3' – 8" |
|
#14 |
(56.67") 4' – 9" |
|
|
|
|
|
#18 |
(73.33") 6' – 2" |
|
|
|
|
|
Grade 60 fy=60,000 psi f 'c=3,600 psi (Class C Concrete) |
|||||
|
#3 |
(9.00") 1' – 0" |
1' – 0" |
1' – 5" |
1' – 2" |
1' – 0" |
|
#4 |
(12.00") 1' – 0" |
1' – 4" |
1' – 10" |
1' – 6" |
1' – 1" |
|
#5 |
(15.00") 1' – 3" |
1' – 8" |
2' – 4" |
1' – 10" |
1' – 4" |
|
#6 |
(18.00") 1' – 6" |
2' – 0" |
2' – 9" |
2' – 3" |
1' – 7" |
|
#7 |
(24.04") 2' – 1" |
2' – 8" |
3' – 8" |
2' –11" |
2' – 1" |
|
#8 |
(31.40") 2' – 8" |
3' – 5" |
4' – 10" |
3' – 10" |
2' – 9" |
|
#9 |
(40.00") 3' – 4" |
4' – 4" |
6' – 1" |
4' – 11" |
3' – 6" |
|
#10 |
(50.64") 4' – 3" |
5' – 6" |
7' – 9" |
6' – 2" |
4' – 5" |
|
#11 |
(62.52") 5' – 3" |
6' – 10" |
9' – 6" |
7' – 8" |
5' – 6" |
|
#14 |
(85.00") 7' – 1" |
|
|
|
|
|
#18 |
(110.00") 9' – 2" |
|
|
|
|
Class B splice – 50 percent or less of the bars spliced at one location* (except conventional slab reinforcing) * Epoxy coated splice lengths by designing engineer (round up to even inch)
|
Description |
Code |
|---|---|
|
Ld ~ basic development length |
A |