Anchor: #BABJGDID

Section 5: Inverted Tee Reinforced Concrete Bent Caps

Anchor: #i1351441

Materials

Use TxDOT Class C concrete (fc ́ = 3.6 ksi) and Grade 60 reinforcing steel. Higher concrete strengths may be required in special cases.

Higher reinforcing steel grades may be used provided their use satisfies requirements in AASHTO.

Anchor: #i1351466

Geometric Constraints

Make inverted tee dimensions the same for all bents supporting the same girder depth on the project.

Keep the top of stem at least 2.5 in. below the bottom of the slab; see standard drawing IGMS.

Anchor: #i1351497

Structural Analysis

In lieu of a more detailed analysis, it is permissible to analyze multiple-column caps as simply supported beams on knife-edge supports at the center of piling or columns. If the column is wider than 4 ft., consider a model that takes the stiffness of the column into consideration.

Distribute the live load to the beams assuming the slab hinged at each beam except the outside beam.

Anchor: #i1351712

Design Criteria

Check limit states using the Strength I and Service I load combinations. Check distribution of reinforcement as required in Article 5.6.7 using Class 1 exposure for moderate exposure conditions and Class 2 exposure for areas where de-icing agents are frequently used or where contact with salt water spray is possible.

Check Article 5.6.3.3 for minimum reinforcement.

For reinforced concrete straddle bents, check the calculated shear, using the Service I Load Combination, against the resistance from Equation C5.8.2.2-1.

For multi-column bent caps, take design negative moments at the center line of the column. For hammerhead bents and multi-column bent caps with columns 4 ft. wide or wider, take design negative moments at the effective face of the column.

Minimize the number of stirrup spacing changes.

The punching shear resistance and hanger reinforcement provided at fascia girders must equal or exceed the factored punching shear demand and hanger reinforcement requirements of the adjacent interior girder.

    Anchor: #XFLIVACL
  • Replace Equation 5.8.4.3.5-1 with the following:

    , with fy not taken larger than 60 ksi.

  • Anchor: #ONHEGOQU
  • ** OR ** Replace Equation 5.8.4.3.5-1 with the following:

    with fy not taken larger than 60 ksi.

  • Anchor: #GVTJSOFY
  • The edge distance between the exterior bearing pad and the end of the inverted T-beam stem shall not be less than 12 inches.
Anchor: #i1351782

Detailing

Provide extra vertical reinforcing across the end surfaces of the stem to resist cracking. Single #5 bars, anchored at each end with hooks and with 6-in. (+/-) spacing, are considered adequate for this purpose for conventional inverted tee cap ends. Do not weld bars together for development of ledge reinforcing. Use anchorage hooks to develop ledge reinforcing.

Use stirrups with a 12-in. maximum spacing. If torsional resistance is explicitly addressed in the design, ensure the stirrup detailing is consistent with AASHTO requirements.

Previous page  Next page   Title page